Standard: | ISO16358 | Test Sample: | Air Conditioner |
---|---|---|---|
Principle: | Air Enthalpy Difference Method | Software: | Included |
Country Of Origin: | China | Warranty: | 1 Year |
High Light: | Psychrometric Air Conditioner Test Equipment,ISO16358 Air Conditioner Test Equipment,ISO16358 Psychrometric Test Chamber |
ISO16358 Air Conditioner Test Equipment Psychrometric Laboratory
ISO16358 Household Air Conditioner Enthalpy Difference Room Psychrometric Testing Laboratory
Air Enthalpy Difference Testing Room for Household Air Conditioner
The chamber design is based on Air enthalpy difference method, use for air conditioner and heat pump combination property testing, it can test the cooling and heating capacity, power consumption, EER, COP, SEER and many performance parameters for test unit. The chamber often use for product development and quality control department, it is necessary facility at manufacturer and certification organization.
The chamber combine outdoor room, indoor room, air condition systems(include cooling, heating and humidify system), air flow measurement systems, electrical controlling systems, computer systems, etc.
The chamber design base on relative international test standard or some local standard, such as ISO5151,EN14852,GB/T7724, we also can customizate according the customer’s special test standard.
Test Unit Capacity Range:
RANGE TYPE
|
Air Flow Rate (m3/h)
|
Cooling&Heating Capacity (W) |
m3/h |
Air-conditioner |
180~2,000 |
Cooling Capacity: 1500~10,000W Heating Capacity: 1500~11,000W |
—— |
Air cooling type Air cooler |
180~2,000 |
Cooling Capacity: 1500~10,000W Heating Capacity: 1500~11,000W |
—— |
Multisplit system Air-conditioner |
NO |
NO |
|
Chamber Extenal Size Details ( Not include the operation room and location for coolers and humidifiers )
Chamber Extenal Size:10000×4000×3200 mm (Lengh×Width×Height)
Indoor Extenal Size:5500×4000×3200 mm (Lengh×Width×Height)
Outdoor Extenal Size:4500×4000×3200 mm (Lengh×Width×Height)
Chamber Ambient Temperature and Humidity Testing Accuracy and Control Accuracy
Indoor |
Temperature 5~45℃ |
Testing Accuracy ±0.1℃ |
Control Accuracy ±0.2℃ |
Humidity 30~90%RH |
Testing Accuracy ±0.1℃(WB) |
Control Accuracy ±0.2℃(WB) |
|
Oudoor |
Temperature -15~60℃ |
Testing Accuracy ±0.1℃ |
Control Accuracy ±0.2℃ |
Humidity 30~90% |
Testing Accuracy ±0.1℃(WB) |
Control Accuracy ±0.2℃(WB) |